| Application |
| LR2-D Series new thermal
relays are suitable in circuit of AC 50Hz voltage up to 660V
and electric power under 45KW for thermal overload protection.It
has temperature compensation component. They can be fixed with
contactor together,and be independently installed as well. |
| |
| Specifications: |
|
Type |
Adjusting
range of current (A) |
Control
power (AC)(KW) |
Plug
in contactor |
220V |
380V |
415V |
440V |
660V |
LR1-D
09301 |
0.1~0.16 |
|
|
|
|
|
LC1-D09-25 |
LR1-D
09302 |
0.16~0.25 |
|
|
|
|
|
LC1-D09-25 |
LR1-D
09303 |
0.25~0.40 |
|
|
|
|
|
LC1-D09-25 |
LR1-D
09304 |
0.40~0.63 |
|
|
|
|
0.37 |
LC1-D09-25 |
LR1-D
09305 |
0.63~1 |
|
|
|
|
0.55 |
LC1-D09-25 |
LR1-D
09306 |
1~1.6 |
|
0.37 |
|
0.55 |
0.7~1.1 |
LC1-D09-25 |
LR1-D
09307 |
1.6~2.5 |
0.37 |
0.55~0.75 |
1.1 |
0.55~0.75 |
1.5 |
LC1-D09-25 |
LR1-D
09308 |
2.5~4 |
0.55~0.75 |
1.1~1.5 |
1.5 |
1.5 |
2.2~3 |
LC1-D09-25 |
LR1-D
09310 |
4~6 |
1.1 |
2.2 |
2.2 |
2.2 |
4 |
LC1-D09-25 |
LR1-D
09312 |
5.5~8 |
1.5 |
3 |
3~3.7 |
3~3.7 |
5.5 |
LC1-D09-25 |
LR1-D
09314 |
7~10 |
2.2 |
4 |
4 |
4 |
7.5 |
LC1-D09-25 |
LR1-D
09316 |
10~13 |
3 |
5.5 |
5.5 |
5.5 |
10 |
LC1-D09-25 |
LR1-D
16321 |
13~18 |
4 |
7.5 |
9 |
9 |
15 |
LC1-D09-25 |
LR1-D
25322 |
18~25 |
5.5 |
11 |
11 |
11 |
18.5 |
LC1-D09-25 |
LR1-D
40353 |
23~32 |
7.5 |
15 |
15 |
15 |
22 |
LC1-D40
50 60 |
LR1-D
40355 |
30~40 |
10 |
18.5 |
22 |
22 |
30 |
LC1-D40
50 60 |
LR1-D
63357 |
38~50 |
11 |
22 |
25 |
25 |
37 |
LC1-D40
50 60 |
LR1-D
63359 |
48~57 |
15 |
25 |
30 |
30 |
45 |
LC1-D40
50 60 |
LR1-D
63361 |
57~66 |
18.5 |
30 |
37 |
37 |
55 |
LC1-D40
50 60 |
LR1-D
80363 |
63~80 |
22 |
33~37 |
40~45 |
40~45 |
59~63 |
LC1-D80 |
|
| |
|