Home >> Product >> Earth leakage circuit breaker series >>F7 Residual Current Device (RCCB)
F7 Residual Current Device (RCCB)
F7 Residual Current Device (RCCB)
  F7 Residual Current Device (RCCB)
 
F7-2P
   
  F7 Residual Current Device (RCCB)   F7 Residual Current Device (RCCB)
 
F7-4P
   
Electrical Technical Data
Standard
IEC/EN 61008
Tripping Time
Type G 10 ms delay
Type S 40 ms delay - with selective disconnecting function
Rated voltage Un
230/400 V, 50/60Hz
Rated currents In
16,25,40,63,80A
Rated tripping current In
30, 100, 300, 500 mA
Sensitivity
type A and type AC
Rated short circuit strength Inc
10 kA
Maximum back-up fuseShort circuit
In = 25-63A 63 A gL In = 80A 80 A gL
Rated breaking capacity Im or Rated
fault breaking capacity Im
In = 25-40A 500 A In = 63A 630 A
In = 80A 800 A
Endurance
electrical life>4,000 operating cycles
mechanical life>20,000 operating cycles
Mechanical Technical Data
Frame size
45 mm
Device height
80 mm
Device width
35 mm (2MU), 70 mm (4MU)
Mounting
on 35mm DIN rail according to EN 50022
Degree of protection built-in switch
IP40
Deg. of protection in moisture-proof
IP54
Upper and lower terminals
open mouthed/lift terminals
Terminal capacity
1 - 25 mm 2
Busbar thickness
0.8 - 2 mm
Tripping temperature
-25¡æ to +40¡æ
   
Copyright © 2006-2007 ZHEJIANG DIXSEN ELECTRICAL CO.,LTD. All Rights Reserved.