| DS series moulded case circuit breaker, it is suitable for
the circuit of AC 50Hz(or 60Hz), rated insulation Voltage 660V,
rated operating Voltage under AC 660V, 250V(DC), rated operating
current 10-800A. It is for distribute energy of electricity
and infrequent switchover in normal conditions. The MCCB rated
current under 400A they are provided with the function of the
protection against overload and short circuit and undervoltage.
The MCCB complies with standard of IEC947-2. |
| Tripping Characteristics Of MCCB |
| Rated Current of release(A) |
Thermodynamic Release(ambient
temp+40°C) |
Operational Current of Magnetic Release(A) |
1.05In(cold state)
inoperative time(h) |
1.30In(heat state)
inoperative time(h) |
| In<=63 |
>=1 |
<1 |
10-50In±20% |
| 63<In<+100 |
>=2 |
<2 |
10In±20% |
| 100<In<=630 |
>=2 |
<2 |
5-10In±20% |
|
| Type |
Rated
Current
(A) |
Rated
insulating
voltage |
Pole |
Rated
operating
voltage |
Ultimate short
circuit breaking
capacity lcu KA |
Operating
performance(times) |
AC380V
(400) |
AC660V
(690) |
DC250 |
AC380V
(400) |
AC660V
(690) |
| DS-125E |
12.5,16,20,
25,32,40,50,
63,80,100,125 |
600V |
3P
4P |
380V
660V |
15 |
- |
- |
7.5 |
- |
| DS-125S |
25 |
- |
20 |
16 |
- |
| DS-160S |
16,20,32,
40,50,63,
80,100,125,
160 |
35 |
8 |
20 |
18 |
- |
| DS-160H |
50 |
10 |
40 |
25 |
- |
| DS-250S |
100,125,
160,180,200,
225, 250 |
35 |
10 |
40 |
18 |
- |
| DS-250M |
50 |
16 |
40 |
30 |
- |
| DS-250H |
65 |
18 |
40 |
48 |
- |
| DS-400S |
200,225,250,
315,350,400 |
35 |
16 |
40 |
18 |
- |
| DS-400M |
50 |
20 |
40 |
30 |
- |
| DS-400H |
65 |
25 |
40 |
48 |
- |
| DS-630S |
400,500,630 |
50 |
20 |
40 |
30 |
- |
| DS-630M |
65 |
25 |
40 |
48 |
- |
| DS-630H |
80 |
30 |
40 |
60 |
- |
| DS-800S |
500,630,
700,800 |
50 |
20 |
40 |
30 |
- |
| DS-800M |
65 |
25 |
40 |
48 |
- |
| DS-800H |
80 |
30 |
40 |
60 |
- |
|
|